Find the cable cross-section (mm²) that keeps voltage drop within your limit, and see the drop for each standard size. Useful for house wiring, solar, IPS and battery cables.

How the calculation works

Voltage drop = k × ρ × L × I ÷ A, where ρ is resistivity (copper ≈ 0.0175 Ω·mm²/m, aluminium ≈ 0.0282), L is the one-way length, I the current and A the cross-section in mm². k = 2 for DC and single-phase (out and back) and √3 for balanced three-phase.

Typical limits

  • 3% for lighting and sensitive loads, 5% total for general circuits is a common guideline.
  • Low-voltage DC (12 V / 24 V solar and IPS battery cables) suffers most: a 0.5 V drop is 4% of 12 V. Keep battery cables short and thick.

Sizing a solar or IPS system? Pair this with the solar system size and IPS size calculators.